SHOP
Verkabelung, PLANET
Industrial RS232/RS422/RS485 to 100Base-FX SFP Converter
Preis auf Anfrage
  • Serial Interface
 –One RS-232 port and one RS-422/485 port to one 100Base-FX Media Conversion  –Cost effective for RS-232/ RS-422/ RS-485 to Ethernet application  –Supports RS-... mehr
Verfügbarkeit
nicht lagernd
Login für mehr Info
Artnr
ICS-2105A
Hersteller
PLANET mehr
Bereits gekauft?
Sie haben Fragen?
Beratung & Verkauf
+43 3172 422 99 0

Produkt-Beschreibung

Beschreibung
Technische Daten
Dokumente
  • Serial Interface
 –One RS-232 port and one RS-422/485 port to one 100Base-FX Media Conversion
 –Cost effective for RS-232/ RS-422/ RS-485 to Ethernet application
 –Supports RS-232 with DB9 interface, 4-wire RS-422 or 2-wire RS-485 with terminal
  block operation
 –Asynchronous serial data rates up to 921600bps
 
  • Ethernet Interface
 –Complies with IEEE 802.3, IEEE 802.3u 100Base-FX standard
 –Supports 100Base-FX multi-mode SC connector, distance up to 2km for ICS-2102
 –Supports 100Base-FX single-mode SC connector, distance up to 15km for ICS-2102S15
 –Supports 100Base-FX single-mode LC connector, distance varies depending on SFP module for
  ICS-2105A
 
  • Smart Functions
 –Standard TCP/IP interface and versatile operation modes
 –Software Protocol supports ARP, ICMP, TCP/IP, UDP, HTTP server, DHCP client, Telnet server/client
 –Built-in IP-based Web interface for remote management
 –Serial Operation mode selected via Web management
 –Pair Connection mode for connecting two serial devices over a network
 –PLANET Smart Discovery utility automatically finds the client devices on the network
 –Firmware upgrade via HTTP protocol
 
  • Hardware
 –LED indicators for easy network diagnose
 –Reset Button on the front panel for resetting to factory default
 
  • Industrial Case / Installation
 –IP30 metal case protection
 –DIN rail and wall mount design
 –12 to 48V DC / 24V AC, redundant power with polarity reverse protect function and connective
  removable terminal block for master and slave power
 –Supports EFT protection 6000 VDC for power line
 –Supports 6000 VDC Ethernet ESD protection
 –-10 to 60 degrees C operating temperature
 
CostCost-effective Solutions of RS-232 / RS-422 / RS-485 for Industrial Ethernet Applications
PLANET ICS-210x Serial over Ethernet Converter series is specially designed to convert serial RS-232, RS-422 or RS-485 communication into Industrial Fast Ethernet networking and help to extend the network distance efficiently and inexpensively. There are SC and LC connectors with single-mode or multi-mode media available in the ICS-210x series for your network needs. The ICS-210x is a time-saving and cost-effective solution for users and SIs to quickly transform its serial equipment to the Ethernet network with no need of replacing the existing serial equipment and software system.
 
Efficiently Extending Network Distance
The ICS-210x series includes models ICS-2102, ICS-2102S15 and ICS-2105A. The ICS-2102 and ICS-2102S15 media converters can extend the deployment distance of serial equipment by 2km and 15km. The ICS-2105A, especially equipped with one SFP fiber slot (mini-GBIC 100Base-FX SFP, Small-Form Factor Pluggable), supports the deployed distance extension from 2km (via multi-mode fiber) up to 120 kilometers (via single-mode fiber) or longer. The ICS-210x series perfectly meets the diverse demands in various industrial network environments and provides reliable network solutions within your budget of installation.
 
Remote Management
The ICS-210x series makes the connected serial equipment become IP-based facilities and able to connect to a TCP/IP network immediately. It also provides Web Management Interface for efficient remote network management. The powerful Web Smart Media Converter series supports application mode and serial operation mode for alarm or IP address connection, which saves the network administrator’s time by detecting and locating network problems without visual inspection of the cabling and equipment. Multiple connection options are available for large networking environment as well.
 
Stable Performance under Difficult Environments
The ICS-210x series provides a high level of immunity against electromagnetic interference and heavy electrical surges which are usually found on plant floors or in curb side traffic control cabinets. The feature of operating temperature range from -10 to 60 degrees C allows the ICS-210x series to be placed in almost any difficult environment.
 
The ICS-210x series is equipped with compact IP30 standard metal case that allows either DIN rail or wall mounting for efficient use of cabinet space. The ICS-210x series also provides an integrated power supply source with wide range of voltages (12 to 48V DC) ideally suitable for worldwide operation with high availability applications requiring dual or backup power inputs.
  

Standard

Abmessungen
135 x 97 x 32 mm
Alarm I/O
Provides one relay output for power failure Alarm relay current carry ability: 1A @ DC 24V
Anschluss
DB9 for RS-232, Terminal Block for RS-422/RS-485
Befestigung
DIN rail kit and wall mount ear
Betriebstemperatur
-10°C - +60°C
Datenrate
300 bps - 921600 bps
Flow Control
Hardware, None
Gehäuse Material
metal case
Lagertemperatur
-20°C bis 75°C
LEDs
System: Power 1, Power 2, Fault TP or Fiber Port: Link / Active Serial Port: Serial port mode, ...
Leistungsaufnahme
Standby 12VDC: 0.34A(4.08W) 24VDC: 0.16A(3.84W) 48VDC: 0.09A(4.32W) Full Load 12VDC: 0.48A(5.76W ...
Luftfeuchtigkeit
10 - 90% RH
Luftfeuchtigkeit Lagerung
5 - 90%, nicht kondensierend
LWL Kategorie
50 or 62.5/125m multi-mode fiber cable 9/125m single-mode fiber cable
LWL Wellenlänge
SFP Modul abhängig
Management
Web Management PLANET Smart Discovery Utility
Max. Kabellängen
2 km up to 120 km (SFP Modul abhängig)
Netzteil
12~48V DC / 24V AC, Redundant power with polarity reverse protection function
Produktfamilie
Serial over Ethernet Converter, Industrial, DIN-Rail
Schutzklasse
IP30
Serielle Schnittstelle
RS-232 x 1 RS-422 / RS-485 x 1
Stabilitäts Test
IEC60068-2-32 (Free Fall) IEC60068-2-27 (Shock) IEC60068-2-6 (Vibration)
Standards & Protokolle
IEEE 802.3 10Base-T IEEE 802.3u 100Base-TX / 100Base-FX EIA/TIA RS-232/422/485
Zertifikate / Zulassungen
FCC Class A, CE Certification Class A